Skip to main content

Kisaju, Kajiado CountyMon – Sat, 8 AM – 5 PM

Class 4 Insulating Matting 36 kV Working

  • Class 4
  • 36 kV working
  • 12.7mm

Class 4 is the highest class stocked: matting for primary substation switchrooms, up to 36 kV working. The maker tests it at 40 kV AC (proof) and 50 kV (dielectric); neither is a working rating.

Duratuf Class 4 is 12.7mm thick, four times the thickness of Class 0, and made to ASTM D178. Its textured surface stays anti-slip underfoot and resists oils, chemicals and abrasion.

Request a QuoteAsk on WhatsApp

Prices are quoted, not published. What the price of electrical insulating matting depends on, and what to send us.

Used for

  • Primary substation switchrooms
  • Substation and switchroom floors

Specifying this? High-voltage insulating matting: choosing a class

Request the technical data sheet for Class 4 Insulating Matting — 36 kV Working.

Black high-voltage insulating rubber matting with printed class markings
Class
4
Max use voltage
36 kV
AC proof test voltage
40 kV
Dielectric test voltage
50 kV
Thickness
12.7mm
Standard
ASTM D178 (maker's data sheet); IEC 61111: ask us to confirm

Sizes stocked

1 size on the stock list. Ask for anything not listed and we will quote to your specification.

  • 1m × 1m × 12.7mm

About Class 4 Insulating Matting — 36 kV Working

Where Class 4 fits on Kenya's network

Class 4, rated to 36 kV working, covers 33 kV equipment: the higher of Kenya Power's two distribution voltages, used at primary substations and for the largest industrial supplies.

Matting adds protection underfoot. It does not replace isolation, permits to work and the rest of the protective equipment.

  • 33 kV switchgear and primary substations
  • 33/11 kV transformer bays
  • Large industrial intakes supplied at 33 kV

Three numbers, and only one of them is yours

Class 4 carries a maximum use voltage of 36 kV, an AC proof test of 40 kV and a dielectric test of 50 kV. The first is the rating; the other two are factory tests, and the difference is the whole point of the class system.

The working voltage is what the mat is rated to stand in front of in service. The test voltages are factory tests the material passed, at margins above that rating, to demonstrate it. Specifying against a test figure puts someone in front of switchgear on a mat rated for less than the duty.

What the mat is, and what it is not

Insulating matting is one layer of protection on the floor of a switchroom. It is not isolation, it is not a substitute for the permit and the proving dead, and it does not make live work safe.

It also only protects the area it covers. A mat that stops short of where an operator actually stands to reach a handle is doing nothing at the moment it is needed.

What is not published here

This is protective equipment, so what is missing matters as much as what is stated. Ask for any of it before you specify, and we will get what the maker can provide.

  • The test certificate for the batch supplied, and its test date.
  • Any retest or in-service inspection interval — that comes from your own safety policy and the standard, not from us.
  • Roll and sheet sizes, and whether it is cut per metre or supplied in fixed mats.
  • Temperature range and shelf life.

Questions we get asked

Can I just buy a higher class to be safe?
You can, and it is not free. Class 4 is 12.7mm thick; the classes above it are thicker again, which matters for door clearances and for anyone walking on it all day. Specify against the highest voltage the mat stands in front of, which is what the class system is for. At 12.7mm this is four times the thickness of Class 0, which is worth checking against door and panel clearances before it is ordered.
Does it come with a test certificate?
Ask for one with the order. We do not publish certificates against these pages, and a certificate that arrives after the mat is laid is no use to an inspection. Tell us at quotation stage that you need it and we will confirm what the maker supplies with the batch.
How often does it need retesting?
We do not publish an interval, and you should be wary of a supplier who does without knowing your installation. That comes from your electrical safety policy and from ASTM D178 or IEC 61111 as your competent person applies them. What we can tell you is what the mat was tested to when it was made.

Matting classes: which one?

GradeMax use / AC proofChoose it for
Class 0 Insulating Mat, 1 kV1 kV / 5 kVLV distribution boards and control panels, up to 1 kV working.
Class 1 Insulating Mat, 7.5 kV7.5 kV / 10 kVDistribution and switchgear running above 1 kV and up to 7.5 kV working.
Class 2 Insulating Mat, 17 kV17 kV / 20 kVMedium-voltage switchgear, up to 17 kV working.
Class 4 Insulating Mat, 36 kV36 kV / 40 kVPrimary substation switchrooms, up to 36 kV working.

Send us your material list

A specification, a BOQ or a photo of the label on the old stock is enough to start. We reply with an itemised quotation.

Or call or WhatsApp 0722 293 517