Class 0 Insulating Matting 1 kV Working

  • Class 0
  • 1 kV working
  • 3.2mm

Class 0 is the matting for low-voltage work: distribution boards and control panels up to 1 kV. Specify it against that maximum use voltage. The maker tests it at 5 kV AC (proof) and 10 kV (dielectric): factory test figures, not ratings to work to.

Duratuf Class 0 is 3.2mm thick and made to ASTM D178. Its textured surface stays anti-slip underfoot and resists oils, chemicals and abrasion.

Request a QuoteAsk on WhatsApp

Prices are quoted, not published. What the price of electrical insulating matting depends on, and what to send us.

Used for

  • LV distribution boards
  • In front of control panels
  • Workshop electrical test benches

Specifying this? High-voltage insulating matting: choosing a class

Request the technical data sheet for Class 0 Insulating Matting — 1 kV Working.

Black high-voltage insulating rubber matting with printed class markings
Class
0
Max use voltage
1 kV
AC proof test voltage
5 kV
Dielectric test voltage
10 kV
Thickness
3.2mm
Standard
ASTM D178 (maker's data sheet); IEC 61111: ask us to confirm

Sizes stocked

1 size on the stock list. Ask for anything not listed and we will quote to your specification.

  • 1m × 1m × 3.2mm

About Class 0 Insulating Matting — 1 kV Working

Where Class 0 fits on Kenya's network

Kenya's low-voltage supply is 415 V three-phase and 240 V single-phase, well inside Class 0's 1 kV working limit. That makes Class 0 the mat for the electrical rooms most sites have, rather than the substation.

Matting adds protection underfoot. It does not replace isolation, permits to work and the rest of the protective equipment.

  • Main LV distribution boards and motor control centres
  • Generator change-over panels
  • Control panels and workshop test benches

Three numbers, and only one of them is yours

Class 0 carries a maximum use voltage of 1 kV, an AC proof test of 5 kV and a dielectric test of 10 kV. The first is the rating; the other two are factory tests, and the difference is the whole point of the class system.

The working voltage is what the mat is rated to stand in front of in service. The test voltages are factory tests the material passed, at margins above that rating, to demonstrate it. Specifying against a test figure puts someone in front of switchgear on a mat rated for less than the duty.

What the mat is, and what it is not

Insulating matting is one layer of protection on the floor of a switchroom. It is not isolation, it is not a substitute for the permit and the proving dead, and it does not make live work safe.

It also only protects the area it covers. A mat that stops short of where an operator actually stands to reach a handle is doing nothing at the moment it is needed.

What is not published here

This is protective equipment, so what is missing matters as much as what is stated. Ask for any of it before you specify, and we will get what the maker can provide.

  • The test certificate for the batch supplied, and its test date.
  • Any retest or in-service inspection interval — that comes from your own safety policy and the standard, not from us.
  • Roll and sheet sizes, and whether it is cut per metre or supplied in fixed mats.
  • Temperature range and shelf life.

Questions we get asked

Can I just buy a higher class to be safe?
You can, and it is not free. Class 0 is 3.2mm thick; the classes above it are thicker again, which matters for door clearances and for anyone walking on it all day. Specify against the highest voltage the mat stands in front of, which is what the class system is for. Where the board runs above 1 kV, Class 1 at 7,500 V is the next step rather than a thicker Class 0.
Does it come with a test certificate?
Ask for one with the order. We do not publish certificates against these pages, and a certificate that arrives after the mat is laid is no use to an inspection. Tell us at quotation stage that you need it and we will confirm what the maker supplies with the batch.
How often does it need retesting?
We do not publish an interval, and you should be wary of a supplier who does without knowing your installation. That comes from your electrical safety policy and from ASTM D178 or IEC 61111 as your competent person applies them. What we can tell you is what the mat was tested to when it was made.

Matting classes: which one?

GradeMax use / AC proofChoose it for
Class 0 Insulating Mat, 1 kV1 kV / 5 kVLV distribution boards and control panels, up to 1 kV working.
Class 1 Insulating Mat, 7.5 kV7.5 kV / 10 kVDistribution and switchgear running above 1 kV and up to 7.5 kV working.
Class 2 Insulating Mat, 17 kV17 kV / 20 kVMedium-voltage switchgear, up to 17 kV working.
Class 4 Insulating Mat, 36 kV36 kV / 40 kVPrimary substation switchrooms, up to 36 kV working.

Send us your material list

A specification, a BOQ or a photo of the label on the old stock is enough to start. We reply with an itemised quotation.