Skip to main content

Kisaju, Kajiado CountyMon – Sat, 8 AM – 5 PM

Class 1 Insulating Matting 7.5 kV Working

  • Class 1
  • 7,500 V working
  • 4.8mm

Class 1 sits between the low-voltage Class 0 and the medium-voltage Class 2: 7,500 V maximum working voltage, at 4.8mm thick. It is the mat for distribution and switchgear that runs above 1 kV but below 7.5 kV.

Specify it against the 7,500 V. The 20 kV that appears on the stock list is the dielectric test voltage on the maker's sheet, and the AC proof test is 10 kV. Both are factory tests, not voltages to stand in front of.

Duratuf Class 1 is Type I, made to ASTM D178, with a fine-ribbed top and textured underside. The surface stays anti-slip underfoot and the rubber resists oils, chemicals and abrasion in daily switchroom use.

Request a QuoteAsk on WhatsApp

Prices are quoted, not published. What the price of electrical insulating matting depends on, and what to send us.

Used for

  • Switchgear and control panels above 1 kV
  • Substation and switchroom floors
  • Site temporary power distribution

Specifying this? High-voltage insulating matting: choosing a class

Request the technical data sheet for Class 1 Insulating Matting — 7.5 kV Working.

A Duratuf Class 1 insulating mat in its wrapping, printed ASTM-D178 Type-I Class 1
Class
1
Max use voltage
7,500 V
AC proof test voltage
10 kV
Dielectric test voltage
20 kV
Thickness
4.8mm
Type
Type I
Surface
Fine ribbed top, textured underside
Colour
Black
Standard
ASTM D178 (maker's data sheet); IEC 61111: ask us to confirm

The 7,500 V working voltage is stated on the manufacturer's roll label and was confirmed by the owner on 30 October 2026 before this page was published. This is protective equipment: no figure here is inferred from the thickness or from the class number, and none should be.

Sizes stocked

1 size on the stock list. Ask for anything not listed and we will quote to your specification.

  • 1m × 1m × 4.8mm

About Class 1 Insulating Matting — 7.5 kV Working

Three voltages, and only one of them is yours

Every class of insulating matting carries two numbers, and confusing them is the mistake that gets people hurt.

  • Working voltage — 7,500 V here. The maximum the mat is rated to stand in front of in service. This is the one you specify against.
  • Test voltages: 10 kV AC proof and 20 kV dielectric here, on the maker's sheet. Factory tests the material passes. It is evidence the mat meets its rating, not permission to work at that level.
  • A mat described only as 20 kV is being described by its dielectric test figure. Ask for the working voltage before you buy it.

Where Class 1 sits in the range

Thickness rises with the rating across the five classes stocked. Match the mat to the highest voltage it will stand in front of, not the nominal or the average.

  • Class 0 — 1 kV working, 3.2mm. LV distribution boards and control panels.
  • Class 1 — 7,500 V working, 4.8mm. This mat.
  • Class 2 — 17 kV working, 6.4mm. Medium-voltage switchgear.
  • Class 3 — 9.5mm. Stocked, but no working voltage is published for it here. Ask before specifying.
  • Class 4 — 36 kV working, 12.7mm. Primary substation switchrooms.

What this page does not tell you

This catalogue publishes what the mat is rated for. It does not publish an in-service inspection interval, a retest period, or guidance on when a mat should be taken out of use — those belong to your own electrical safety rules and the standards you work to, not to a supplier's product page.

Matting is the last line of defence in front of live equipment. Treat anything it is asked to do beyond its published rating as a question for the person responsible for that safety system.

Questions we get asked

The stock list says 20 kV. Can I use it at 20 kV?
No. 20 kV is the dielectric test voltage on the maker's sheet, and the AC proof test is 10 kV. Neither is a working limit. The maximum use voltage is 7,500 V and that is the figure to specify against. If the equipment runs above 7.5 kV, Class 2 at 17 kV or Class 4 at 36 kV is the mat you need.
How is it supplied?
1m wide, cut per metre from 10m rolls, so you can take the run your switchroom floor needs rather than a fixed sheet.
What is the difference between Class 1 and Class 2?
The rating and the thickness. Class 1 is 7,500 V working at 4.8mm; Class 2 is 17 kV working at 6.4mm. Both are Duratuf, both made to ASTM D178. Choose on the voltage the mat will stand in front of.

Matting classes: which one?

GradeMax use / AC proofChoose it for
Class 0 Insulating Mat, 1 kV1 kV / 5 kVLV distribution boards and control panels, up to 1 kV working.
Class 1 Insulating Mat, 7.5 kV7.5 kV / 10 kVDistribution and switchgear running above 1 kV and up to 7.5 kV working.
Class 2 Insulating Mat, 17 kV17 kV / 20 kVMedium-voltage switchgear, up to 17 kV working.
Class 4 Insulating Mat, 36 kV36 kV / 40 kVPrimary substation switchrooms, up to 36 kV working.

Send us your material list

A specification, a BOQ or a photo of the label on the old stock is enough to start. We reply with an itemised quotation.

Or call or WhatsApp 0722 293 517